Foul and Surface Water, Kept Apart
Most jobs have two kinds of drainage. Foul water comes from toilets, baths, showers, sinks, dishwashers and washing machines. Surface water is rain from roofs, drives and paved areas. They run in separate pipes, and the drawing shows where each one goes.
Approved Document H, the government guidance behind the drainage part of the Building Regulations, puts surface water into a soakaway or other infiltration system wherever that is practicable. A watercourse comes next, and that can need consent from the Environment Agency. A sewer is the last choice.
Falls matter as much as the route. The same guidance sets a minimum fall of 1:80 for a 100mm foul drain serving at least one WC, and a minimum of 1:100 for 75mm and 100mm rainwater drains. We set out each run from the levels on the drawing and check the fall along the trench as we dig, so nothing ends up flat or back falling.